Categories
CVE-2017-7574 critical CVSS 9.8

Vulnerability in Schneider Electric SoMachine Basic (CVE-2017-7574)

Summary

Vulnerability in Schneider Electric SoMachine Basic (CVE-2017-7574). Successful exploitation can lead to full system takeover.

Original description

The description as published by the source.

Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.

Source: NIST National Vulnerability Database NVD GitHub Advisory

Auto-generated summary

Assembled by SecPulse from the source data (CVSS, CWE, affected versions) using templates — no AI involved. Check the original description and references below for exact details.

A vulnerability tracked as CVE-2017-7574 has been found in Schneider Electric SoMachine Basic.
Successful exploitation can lead to full system takeover. CVSS score: 9.8/10.
What to do: apply the vendor's official patched release.
If unsure, ask your IT team or search "Schneider Electric SoMachine Basic CVE-2017-7574" on the vendor's site.

CVE-2017-7574 (Schneider Electric SoMachine Basic) — CWE-321 / CVSS v3 9.8
Attack vector: remote (network-reachable) / unauthenticated / no user interaction
Plan: 1) Audit SBOM/dependencies, 2) Stage→prod upgrade, 3) Add WAF/proxy monitoring on affected endpoints, 4) Hunt IOCs in logs.
Refs: see the GHSA / vendor advisory / patched release linked on this page.

❓ What is the problem

A vulnerability (CWE-321) exists in Schneider Electric SoMachine Basic.

📍 Affected scope

Check the vendor advisory for the affected versions of Schneider Electric SoMachine Basic.

🔥 Severity

Severity: Critical (CVSS 9.8/10). Successful exploitation can lead to full system takeover.

🔧 How to fix

Update to the patched release per vendor advisory.

🛡️ Workaround

Until the patch is applied: disable the affected feature, apply WAF rules, or restrict access via network ACLs.

🔍 Detection

Search webserver/proxy logs for unusual request patterns matching this CVE's known IOCs. Audit SBOM/dependencies to find affected services.

Response actions

Concrete steps and command examples for SOC/SRE teams to execute in order

  1. 1
    Identify exposure identify
    Audit SBOM/dependencies for affected components.

    資産台帳・SBOM・依存マニフェストで Schneider Electric SoMachine Basic を使っているサービスとバージョンを洗い出す。

  2. 2
    Post-deployment verification verify
    Confirm patched version is live in production

    パッチ適用後、ステージングで PoC または同等の悪用パターンを再現して脆弱性が閉じたことを確認。本番ではアクセスログ・WAF でアラート再発が無いか継続監視。